LRIC+ Series


PRODUCTS


LRIC+ Series

Line Cord Connected, High-Frequency
Noise Filter with Transient Protection

A series-connected high-frequency noise filter with transient protection.
Overview
Single Phase Active Tracking Filter, for line cord connected loads up to 15 Amps

The Islatrol LRIC+ is a direct plug-in, series-connected, high-frequency noise filter with transient protection for critical loads up to 15 amps.  Islatrol LRIC+ applications include industrial or office equipment, and computers placed in harsh environments.

Features
  • Typically reduces normal mode transients to +/-2 volts
  • Surge current capacity — 45,000 Amps
  • Transient protection in all modes: line to neutral, line to ground, and neutral to ground
  • LED power indication
  • UL 1283, CSA recognized
  • 10 year warranty
Technical Specification

MCOV

  • 120 Volt: 150 VRMS
  • 240 Volt: 275 VRMS
  • Line Frequency: 47 - 63 Hz

Response Time

  • Normal Mode: < 0.5 ns
  • Common Mode: < 5 ns

Operating Temperature

  • -40°C to +45°C at Full Load
  • Derate Linearly to 60% at +70ºC

Operating Humidity: 0% to 95%

Peak Surge Current Capability (8 x 20 μs)

  • Line to Neutral: 15,000 Amps
  • Line to Ground: 15,000 Amps
  • Neutral to Ground: 15,000 Amps

Load Surge Current Rating

  • 10mSec: 5 x Nominal
  • 1 sec: 3 x Nominal
  • 10 sec: 2 x Nominal

Packaging

  • High Impact Plastic Case
  • Vacuum Impregnated Magnetics
  • Epoxy Encapsulated

Frequency Response (Forward-Reverse)

  • Normal Mode: 100 kHz to 50MHz - 90 dB Min
  • Common Mode: 5MHz to 50MHz - 60 dB Min

 

Typical Category A Ringwave (6kV,200A,100kHz)

Model 

Normal

Common

 IC+102 / LRIC+102  1.0 / 0.9  302 / 287
 IC+105 / LRIC+105  0.7 / 0.8  292 / 307
 IC+107 / LRIC+107  0.7 / 0.7  302 / 293
 IC+115 / LRIC+115  0.7 / 0.7  304 / 306
 IC+130 / IC+202  0.5 / 1.1  306 / 536
 IC+205 / IC+207  1.5 / 0.8  628 / 616
 IC+215 / IC+230  0.6 / 0.9  572 / 566

Typical Category B Ringwave (6kV,500A,100kHz)
Model Normal Common
 IC+102 / LRIC+102  178 / 188  302 / 285
 IC+105 / LRIC+105  162 / 191  291 / 300

 IC+107 / LRIC+107

 173 / 190  300 / 298
 IC+115 / LRIC+115  153 / 149  307 / 309
 IC+130 / IC+202  241 / 302  299 / 532
 IC+205 / IC+207  378 / 336  594 / 596
 IC+215 / IC+230  272 / 342  548 / 578

 

Note: Allmeasurements in volts. IEEE test results with no AC applied. Normalmode—L1-N or L1-L2; Commonmode—L-G, N-G or L1-G, L2-G.

Contact Support