ASCO 7000 Series Withstand and Close-On Ratings 

Withstand and Close-On Ratings for all 7000 Series Products 1, 2

Switch Rating(Amps)
UL 1008 Withstand and Close-On Ratings 1
Ratings (RMS Symmetical)
Recommended Fuses
Short Time Ratings @ 480V 4
Transfer
Switches
Bypass Switches
"Specific" Breaker2 Rating
Volts Maximum
"Any" Breaker3
Volts Maximum
Current-Limiting Fuse Rating
Volts Maximum
Max Size, A
Class
Rating
(RMS Sym), A
Duration
30
-
10kA
600V
100kA
480V
60
J
N/A
-
70, 100, 125, 150
-
22kA
480V
10kA
600V
200kA
480V
200
J
N/A
-
200
-
22kA
480V
10kA
480V
200kA
480V
200
J
N/A
-
230
-
22kA
480V
10kA
480V
100kA
480V
300
J
N/A
-
260, 400, 600
150, 200, 230, 260, 400, 600
50kA
480V
65kA
240V
200kA
600V
600
J
N/A
-
42kA6
480V
800
L
42kA
600V
35kA
600V
800 - 1200
800 - 1200
65kA
600V
50kA
600V
200kA
600V
1600
L
36kA
18
1600, 2000
1600,2000
125kA 7
480V
100kA5
600V
200kA
600V
3000
L
42kA
18
2600,3000
3000
-
600V
100kA
600V
200kA
600V
4000
L
42kA
18
4000
4000
-
600V
100kA
600V
200kA
600V
5000
L
85kA
8
65kA
30

Notes:

1) All WCR values indicated are tested in accordance with the requirements of UL 1008. See ASCO Pub 1128 for more WCR information.
2) Application requirements may permit higher WCR for certain sizez of switches. Contact ASCO for guidance if application requires higher WCR.
3) Based on 3 cycles for 260-4000A and 1.5 cycles for 30-230A switches. Applicable to circuit breakers with instaneous trip elements.
4) Short Time ratings are provided for applications involving circuit breakers that utilize trip delay settings for system selective coordination.
5) Optional front connected service(Accy 40MY and 40NY) limits 1600 and 2000A G Frame switches to 85kA Any Breaker rating.
6) J Frame switches utilizing overlapping neutral(code "C") are limited to 35kA Any Breaker rating at 480V.
7) 7000 Series Bypass Switches ONLY.