| Primary Application |
Commercial |
Modular Commercial and Critical |
Custom / Mission Critical |
| Low Voltage (LV) |
Up to 600V |
Up to 600V |
Up to 600V |
| Medium Voltage (NV) |
N/A |
Up to 13.8kV |
Up to 13.8kV |
| Standby |
Yes |
Yes |
Yes |
| Prime Power |
Yes |
Yes |
Yes |
| Utility Parallel |
N/A |
N/A |
Yes |
| Open-Transition |
Yes |
Yes |
Yes |
| Closed Transition / Soft Load/Unload |
N/A |
N/A |
Yes |
| Peak Shaving |
N/A |
N/A |
Yes |
Momentary (0.1s or less) closed-transition |
N/A |
Yes |
Yes |
| Number of Generators |
2 or 4 |
up to 8 |
Any |
| Main Bus Amp size available |
3,000; 6,000 or 10,000A |
3,000; 6,000 & 10,000A |
3,000; 6,000 & 10,000A |
Switchgear construction/label (UL Standard) |
891 Std . 1558 Opt. |
1558 Std. / 891 Opt. |
1558, 891, MV |
| Bus Bracing level, kAIC |
100 |
100 |
Up to 200 |
Maximum Generator Breaker Frame size |
4,000A |
5,000A |
5,000A |
| Generator Paralleling Breakers |
2 per cubicle |
2 per cubicle |
1 or 2 per cubicle |
| Cicuit Breaker Manufacturer |
Square D |
Square D or Siemens |
Any |
| Utility Tie Circuit Breaker available |
N/A |
N/A |
Optional |
| Utility Circuit Breaker |
N/A |
N/A |
Optional |
| Master Controls available |
N/A |
Yes |
Yes |
| Master Controls Touch Screen |
N/A |
Yes |
Yes |
Master Touch Screen Pages (available screens) |
N/A |
Yes |
Yes |
| Engine - Generator Info Screen |
N/A |
N/A |
Yes |
| Master PLC Type |
Horner |
GE Fanuc 90-30 |
GE Fanuc* |
| Hot Standby Master PLC |
N/A |
Optional 90-30 |
GE Fanuc* |
| Hot Standby Synchronized Master PLC |
N/A |
N/A |
GE Fanuc RX7i |
| Redundant Master I/O available |
N/A |
N/A |
Optional |
| Bus Load Optimization |
N/A |
Yes |
Yes |
| Load Demand |
Optional |
Yes |
Yes |
| Load Shed/Add |
ATS Based |
ATS Based |
Custom |
| Max Number of ATSs for load control |
8 per Gen. |
32 Std., 64 Opt. |
Any |
| Generator Controller type |
Digital |
Digital |
Digital |
| Generator Controller redundancy |
N/A |
Yes |
Yes |
| Generator Controls Touch Screen |
N/A |
Optional |
Yes |
| Generator Control Section Configuration |
2G |
1G/2G |
1G/2G |
| Ethernet Remote Diagnostics |
N/A |
Yes |
Optional |
| Analog Diagnostic Modeml |
N/A |
Yes |
Optional |
| Compression type lugs |
N/A |
Optional |
Optional |
| Bus Duct Risers available |
N/A |
N/A |
Optional |
| PCS Optional Accessories |
Yes |
Yes |
Custom |
| Digital |
Yes |
Yes |
Yes |
| Analog and Digital |
N/A |
N/A |
Yes |
| Circuit Breaker Brand choice avaliable |
Square D |
Square D or Siemens |
Any |
| Manually Operated Distribution Circuit Breakers available |
Optional |
Optional |
Optional |
Electrically Operated Distribution Circuit Breakers available |
N/A |
N/A |
Optional |
| Type 1 |
Yes |
Yes |
Yes |
| Type 3R |
Yes |
Yes |
Yes |
| Remote Annunciator Panel, LED type |
N/A |
Yes |
Yes |
Remote Annunciator Panel, Touch Screen type |
N/A |
Yes |
Yes |
| 40" LCD Display with PC |
N/A |
N/A |
Yes |
| Remote Monitoring |
N/A |
Optional |
Optional |
| PowerQuest Remote Desktop |
N/A |
Optional |
Optional |
| NFPA Test Report Package |
N/A |
Yes** |
Yes |
| Serial RS-485 Modbus® TRU |
Yes |
Yes |
Yes |
| Ethernet, Modbus® TCP |
Optional |
N/A |
Yes |
| Ethernet, BACnet, from PowerQuest computer |
N/A |
Yes |
Optional |
| Serial Modbus® RTU (RS485/232 ports) |
Yes |
Yes |
Yes |
*GE Fanuc 90-30 standard, RX3i optional, and RX7i optional
**Available only with PowerQuest Remote Desktop
300 Series offers a compact, cost-efficient package to parallel generators and manage loads. A variety of distribution breakers and structures are available to meet site specific needs. With over fifty systems in operation, this design offers refined reliability at a competitive cost.
4000 Series provides the features most commonly required in high reliability systems for mission critical and healthcare facilities. Touchscreen based controls with industrial grade master PLC's are combined with
a wide variety of structural and controls options to offer predictable reliability.
7000 Series provides custom systems designed per the customer's specifications. Common requirements include; multiple utilities, complicated sequences, redundant processors, SCADA, tie breakers, redundant communications, complicated protective relay schemes, graphic mimic, and other special hardware and control requirements.