PRODUCTS


Liebert® APS™ On-Line UPS,
5-20kVA

Emerson Network Power > United States > Products > AC Power and UPS > Network UPS > Liebert APS On-line UPS, 5-20 kVA

The Liebert APS UPS provides mission-critical availability ensuring your critical IT functions – and your business – will be available and running as expected through power disruptions, fluctuations and outages.

The Liebert APS UPS adapts efficiently and effectively as the needs of your users and core business power requirements change. The UPS offers capacity on demand with FlexPower core modules – allowing you to change capacity in 5kVA/4.5kW increments up to 20kVA.

  • True on-line double conversion UPS
  • Transformer-free and transformer-based models
  • User installable, hot-swappable capacity and battery modules
  • Internal redundancy capability (N+2/20kVA)
Features

Low Total Cost of Ownership

  • Industry-leading efficiency: 92% for transformer-free systems and up to 89.9% for transformer based systems.
  • Scalability that allows you to cost-effectively add power capacity or battery modules as needed.
  • Modular batteries, controls and power components to help reduce maintenance costs with user replacement.
  • Two year hassle-free factory warranty program for repair or replacement of your Liebert APS UPS.
  • Module-level redundancy eliminates the expense of purchasing and planning for additional cabinets.
  • Reduced installation time and cost because units are shipped pre-configured and factory tested, no need for on-site assembly.
  • Everything you need for efficiency and availability in one box: power modules, batteries, maintenance bypass, and distribution in a single, small-footprint cabinet.
  • Integral battery monitoring with temperature compensated charging to prolong battery life and help reduce replacement costs.

Reliability and Serviceability

  • Internal redundancy capability (N+2/20kVA) enhances reliability and provides multiple layers of power protection.
  • No single point of failure - Full redundant design allows the critical load to run on conditioned power if there is a failure of any component in the system.
  • Configurable design allows you to customize the Liebert APS UPS for your desired level of capacity and redundancy.
  • Fault-tolerant design, enables the power, battery and control modules to take themselves offline if there is a problem, without sacrificing overall system integrity.
  • Superior overload capabilities, able to provide conditioned power to temporary overloads without transfers to/from bypass power.
  • Internal wrap-around maintenance bypass and frame-level bypass with independent controls in separate assembly provide higher reliability and availability.

Flexibility

  • Capacity on demand with FlexPower™ core modules that allow you to change capacity as needed in 5 kVA/4.5 kW increments - without powering down.
  • More real kW - 0.9 power factor provides more real power to support the I.T. load than other solutions in this size range.
  • Isolated and non-isolated models to provide the right solution for your power protection needs.
  • Integrated distribution PODs allow selection of a variety of distribution options to meet application requirements.
  • Trellis™ platform connectivity, so the Liebert APS can easily be integrated with this robust, real-time data center optimization solution.
  • Three Liebert Intellislot® ports allow integration and communication with a variety of infrastructure management solutions, leading to better power optimization and visibility.
  • Optional matching external battery cabinets provide longer battery run times to protect against sustained power issues.
  • Installation Flexibility – use on raised floors, traditional flooring, or in rack enclosures.
  • Large input voltage window, which minimizes transfer to battery and increases battery life; low line transfer can range down to 110v.
  • Wide range of use, with the ability to be installed on raised floors, traditional flooring, or in rack enclosures

Ideally Suited For

  • Small-to-medium-sized data centers
  • Network closets
  • VoIP
Benefits

Liebert® APS™ UPS

Parameters

Units

10
Bay

16
Bay

12 Bay

16 Bay

10 Bay

16 Bay

Xfmr-free

Xfmr-based

Xfmr-free
dual inverter

Frame Rating

kVA

15

20

15

20

15

20

kW

13.5

18

13.5

18

13.5

18

General & Environmental

Conducted and
radiated EMC levels

 

IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A,
FCC Part 15 Class A

Compliant safety standards

 

IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22.2 No. 107.1

UL 1778 4th Ed and
CSA 22.2 No. 107.1

Compliant immunity standards

 

IEC/EN/AS 61000-4-2, 3, 4, 5, 6

Environmental

 

WEEE and ROHS2 (6 by 6), REACH Compliant

Mechanical

Units

10
Bay

16
Bay

12
Bay

16
Bay

10 Bay

16 Bay

Width

mm (in)

440 (17)

440 (17)

440 (17)

440 (17)

440 (17)

440 (17)

Depth

mm (in)

800 (32)

850 (34)

800 (32)

850 (34)

800 (32)

850 (34)

Height

mm (in)

695 (27)

970 (38)

1060 (42)

1240 (49)

695 (27)

970 (38)

Weight

(frame rating populated)

Unit weight

kg (lbs)

256.3 (565)

317.5 (700)

360.6 (795)

417.3 (920)

256.3 (565)

317.5 (700)

Shipping weight

kg (lbs)

274.4 (605)

335.7 (740)

378.7 (835)

435.4 (960)

274.4 (605)

335.7 (740)

Environmental

Units

 

Operating
temperature

°C (°F)

0 - 40 (32 - 104)

Relative humidity

%

0 - 95%, non-condensing

Altitude

m (ft)

3000 (10000) @25°C (77°F)

Efficiency (AC-AC)

%

91.8-92.0

91.6-92.0

88.5-89.9

88.6-89.7

90.4-91.0

90.0-91.0

Nominal heat dissipation

BTU/Hr (max)

4208

5747

5528

7965

4904

6768

Input Data

Units

 

 

Nominal input voltage

VAC

200/208/220/230/240; Single Phase

200/100, 208/120, 220/110, 230/115, 240/120;

Single Phase

380/400/415; 3 Phase

 

Input voltage range

VAC

The input voltage range based on the ouput loading, refer to User Manual

Power factor

Cos

Single-phase input, > 0.99; three-phase input, > 0.95

Single-phase input, > 0.99

Input
frequency range

Hz

40 to 70 auto-sensing

Battery Module

Units

 

Battery capacity

W

36W @ 15min-rate to 1.67V per cell @25°C (77°F)

Backup time
(full load)

minutes

5 (for non-redundant system which has equal number of battery strings and power modules)

Maximum charge current (full load)

Amps

Power module internal charger: 1.8A / Charger module: 10A

Nominal voltage

VDC

144

Recharge time

Hrs

< 5 to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)

Output Data

Units

 

Output voltage

VAC

200/208/220/230/240;

Single Phase

100/100/173/200, 110/110/190/220, 115/115/199/230, 120/120/208/240;
Single Phase

200/100, 208/120, 220/110, 230/115, 240/120; Single Phase

Voltage regulation

%

±3

Voltage stability
(100% step load)

%

±7

Voltage
Recovery time

ms

≤ 60

Voltage distortion

%

≤ 3, linear load

≤ 5, non-linear load

≤ 7, non-linear load

≤ 5, non-linear load

Output frequency

Hz

50/60

Output overload capability

%

< 104% continuous

105% - 130% for 1 min

131% - 150% for 10 sec

151% - 200% for 1 sec

> 201% for 250 msec

Specifications

Local Liebert Representative
Contact your local Liebert NA Representative at your location.

Network and Rack UPS Products
Contact our support department about your Liebert network and rack UPS system.

Sales, Service, and Support
1-800-222-5877
Outside the US: +800-1155-4499

Contact Support
ENERGY STAR®
Qualified UPS models meeting the EPA’s requirements use an average of 35% less energy than their standard counterparts.
Learn More
Capacity on Demand: A Blueprint for Flexible Power Growth
Learn how the new Liebert® APS™ UPS with FlexPower™ technology provides a solution for cost-effective power growth in the data center.
View Infographic