Firetrol FTA2000 Medium Voltage Fire Pump Controller

E2 Class Medium Voltage Controller

Firetrol FTA2000 combined automatic and manual class E2 medium voltage controllers are intended for starting of squirrel cage motors driving listed fire pumps.
Product Information/Sales
Overview
Firetrol® FTA2000 combined automatic and manual class E2 medium voltage controllers are intended for starting of squirrel cage motors driving listed fire pumps. Maximum ratings are as follows:

Max. HP 3-Phase Voltage
1500 2200-2500
2000 3200-3500
2500 4000-5000
3500 5000-7200


Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA20, Installation of Centrifugal Fire Pumps, and NFPA70, National Electrical Code.
Features
The following are included as standard with each controller:
  • Isolating Switch - NEMA Rating, 7200 Volts, 400 Amps with external operating handle with electrical and mechanical interlocks to prevent opening of the high voltage compartment door with the isolating switch or the main contactor closed. Interlocks prevent opening the isolating switch with the main contactor closed.
  • Vacuum Contactor - NEMA Rating, 7200 Volts, 400 Amps
  • Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition
  • Built-in Start and Stop push-buttons to bypass automatic start circuits
  • Normal-Off-Test Selector Switch - Internally mounted for functional test of control system only, requires that isolating switch be open and a separate 120 volt AC power source be supplied.
  • Door mounted display/interface panel featuring a 128 x 64 pixel backlit LED Graphical Display, Membrane Type User Control Push-buttons and easy to read LED Indicators for:
  • POWER AVAILABLE
  • ALARM
  • SYSTEM PRESSURE LOW
  • PUMP RUNNING
  • DELUGE OPEN
  • REMOTE START
  • INTERLOCK ON
  • FAIL TO START
  • MOTOR OVERLOAD
  • PHASE FAILURE
  • PHASE REVERSAL
  • AUTOMATIC SHUTDOWN DISABLED
  • OVERVOLTAGE
  • UNDERVOLTAGE
  • Minimum Run Timer / Off Delay Timer
  • Daylight Savings Time Option
  • Weekly Test Timer
  • Elapsed Time Meter
  • Digital Pressure Display
  • USB Host Controller and Port
  • Solid State Pressure Transducer
  • Data Log
  • Event Log (3000 Events)
  • True RMS Metering with simultaneous 3 phase display of amps and volts
  • Disk Error message
  • Disk Near Full message
  • Pressure Error message
  • Motor Over 320% message
  • Local Start message
  • Remote Start message
  • Emergency Start message
  • Fail To Start message
  • Undervoltage message
  • Overvoltage message
  • NEMA Type 2 enclosure
  • Suitable for use as Service Equipment
Options/Modifications
SPECIAL ENCLOSURES
-T NEMA Type 3R (IEC IP14), Painted Steel
-E NEMA Type 4 (IEC IP56), Painted Steel
-F NEMA Type 4X (IEC IP56), #304 Stainless Steel, Unfi nished**
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, Painted Finish
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, Unfinished**
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam Welded, #316 Stainless Steel, Polished and Brushed Finish
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel Painted Finish
-G NEMA Type 12 (IEC IP52), Painted Steel ** Unfi nished (Not painted, polished or brushed).
ANTI-CONDENSATION SPACE HEATERS
-H 120 Volt Space Heater
-J 120 Volt Space Heater With Thermostat
-K 120 Volt Space Heater With Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater With Thermostat
-N 240 Volt Space Heater With Humidistat
Pressure Transducers
-B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
ALARMS
-AC Extra contacts (normally open & normally closed) for remote indication, pump operating
-AF Audible and Visible low pump room temperature alarm
-AG Built-in reservoir low alarm
-AH Audible low suction pressure alarm
-AM Contacts for remote indication, pump fail to start
-AV Contacts for remote indication, low pump room temperature
-AW Contacts for remote indication, reservoir low
-AY Contacts for remote indication, low suction pressure
-AZ Low pump room temperature switch, mounted and wired
-BW Extra contacts for remote indication, phase failure/phase reversal
-BY Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable auto/manual reset, audible, visible and remote alarms, initiating pressure switch not included)
-CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch)
-EG Visible Relief Valve Discharge alarm
-EH Contacts for remote indication, relief valve discharge
-EJ Visible fl ow meter on alarm 1
-EK Contacts for remote indication, flow meter on
-KH Contacts for remote indication, common output for any alarm
-JR Visible jockey pump running indication
-JT Visible fuel spill alarm
-P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump
-PB Built-in low system pressure visible alarm with manual reset
-PE Contacts for remote indication, low system pressure
-PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
MISCELLANEOUS
-BAT 220-240 Volt Test Circuit
-GZ 50 Hz Operation
-PY Motor space heater output contacts
-S Tropicalization
-SEI Seismic Certifi cation (in accordance with IBC)
-ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up)
-ZPN 5150 Ethernet Connectivity Module (Allows users to monitor limited controller status via a single computer or over a computer network)
-ZPM Serial Modbus RTU Communications Protocol (Allows users to monitor all aspects of the controller status via a RS485 communications network (system integration required). (Includes RS485 to twisted pair breakout module, optical isolation module (4000 ft. range), DC power supply and customer connection terminal blocks).