Emerson | Firetrol FTA2000 Medium Voltage Fire Pump Controller

 
PRODUCTS

Firetrol FTA2000 Medium Voltage Fire Pump Controller

E2 Class Medium Voltage Controller

Firetrol® FTA2000 combined automatic and manual class E2 medium voltage controllers are intended for starting of squirrel cage motors driving listed fire pumps. Maximum ratings are as follows:

Max. HP 3-Phase Voltage
1500 2200-2500
2000 3200-3500
2500 4000-5000
3500 5000-7200


Firetrol fire pump controllers are listed by Underwriters' Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA20, Installation of Centrifugal Fire Pumps, and NFPA70, National Electrical Code.

The following are included as standard with each transfer switch:

  • Thermal magnetic circuit breaker
  • 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held
  • ASCO® Group 5 Control module providing for the following:
    -Door mounted operator interface panel with 4 line LED display
    -In-phase monitor
    -Programmable engine exerciser
    -Transfer switch data logging
    -Differential voltage sensing on all phases of the normal power source
    -Voltage sensing of the emergency power source
    -Frequency sensing of the emergency power source
    -Transfer time delay to compensate for momentary power outages of the normal source
    -Retransfer from emergency to normal source is automatically delayed unless the emergency source fails
    -Cool-down timer for unloaded running of the generator set after retransfer to the normal power source
    -Instantaneous retransfer to normal if the emergency source fails and the normal source is available
    -3 second transfer restart delay to reduce current surges when transferring to or from the emergency source
    -NO and NC engine control contacts to start the generator set when the normal power source fails
  • Transfer Switch Normal LED
  • Transfer Switch Emergency LED
  • Emergency Isolating Switch Open LED
  • Test Selector Switch
  • Transfer By-pass Switch
  • Silence Alarm Pushbutton
  • Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms
  • Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators
  • NEMA Type 2 enclosure (IEC IP11)
Features
SPECIAL ENCLOSURES
-T NEMA Type 3R (IEC IP14), Painted Steel
-E NEMA Type 4 (IEC IP56), Painted Steel
-F NEMA Type 4X (IEC IP56), #304 Stainless Steel, Unfi nished**
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, Painted Finish
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, Unfinished**
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam Welded, #316 Stainless Steel, Polished and Brushed Finish
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel Painted Finish
-G NEMA Type 12 (IEC IP52), Painted Steel ** Unfi nished (Not painted, polished or brushed).
ANTI-CONDENSATION SPACE HEATERS
-H 120 Volt Space Heater
-J 120 Volt Space Heater With Thermostat
-K 120 Volt Space Heater With Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater With Thermostat
-N 240 Volt Space Heater With Humidistat
Pressure Transducers
-B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
ALARMS
-AC Extra contacts (normally open & normally closed) for remote indication, pump operating
-AF Audible and Visible low pump room temperature alarm
-AG Built-in reservoir low alarm
-AH Audible low suction pressure alarm
-AM Contacts for remote indication, pump fail to start
-AV Contacts for remote indication, low pump room temperature
-AW Contacts for remote indication, reservoir low
-AY Contacts for remote indication, low suction pressure
-AZ Low pump room temperature switch, mounted and wired
-BW Extra contacts for remote indication, phase failure/phase reversal
-BY Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable auto/manual reset, audible, visible and remote alarms, initiating pressure switch not included)
-CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch)
-EG Visible Relief Valve Discharge alarm
-EH Contacts for remote indication, relief valve discharge
-EJ Visible fl ow meter on alarm 1
-EK Contacts for remote indication, flow meter on
-KH Contacts for remote indication, common output for any alarm
-JR Visible jockey pump running indication
-JT Visible fuel spill alarm
-P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump
-PB Built-in low system pressure visible alarm with manual reset
-PE Contacts for remote indication, low system pressure
-PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
MISCELLANEOUS
-BAT 220-240 Volt Test Circuit
-GZ 50 Hz Operation
-PY Motor space heater output contacts
-S Tropicalization
-SEI Seismic Certifi cation (in accordance with IBC)
-ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up)
-ZPN 5150 Ethernet Connectivity Module (Allows users to monitor limited controller status via a single computer or over a computer network)
-ZPM Serial Modbus RTU Communications Protocol (Allows users to monitor all aspects of the controller status via a RS485 communications network (system integration required). (Includes RS485 to twisted pair breakout module, optical isolation module (4000 ft. range), DC power supply and customer connection terminal blocks).
Options/Modifications
Brochures and Data Sheets
Product Information/Sales
Diagrams and Drawings
Technical Information
Product Information/Technical
Firetrol
Service Support