ASCO Service Entrance Rated Switchboard

The ASCO Service Entrance Rated transfer systems are designed for automatic switching of loads between the utility source and an alternate source of power. The transfer system also contains a disconnect device on the normal source, including a disconnect link on the utility neutral, and a disconnect link between neutral and ground. If the utility source is Y connected, the voltage is greater than 250 volts phase to neutral and the system continuous current is greater than 1000 amperes, the utility disconnect device will be equipped with ground fault trip.

Product Features

    • The utility disconnect device will be equipped with ground fault trip if the voltage between neutral and ground is greater than 250 volts, and the continuous current is greater than 1000 amperes
    • Disconnect link for the utility neutral bus
    • Disconnect link between the neutral bus and the ground bus
    • Meets all NEC requirements for service entrance rating, and is labeled to UL 891 standards
    • Available up through 4000 amperes using ASCO 7000 series automatic transfer switches. 7ATS, 7ATB, 7ACTS and 7ACTB