Edco OPX Series


PRODUCTS

Edco OPX Series

Intercom/Speaker Punch Block Surge Protection

The Edco OPX surge protectors are specifically designed for medium exposure applications. The protectors can be used on pairs inside a building or outside the building in conduit up to 500 feet. These protectors are intended to be used in conjunction with the Edco MGB Ground Rail and a standard MI-50 Punch Down Block.

  • Over current protection
  • Replaces bridging clips on M1-50 bock
  • UL 497B listed
  • Utilizes MGB grounding rail
  • Test point accessible
  • 5-year warranty
Features
  • Low cost
  • No series resistance
  • Durable, solid-state construction
Benefits
  • Operating Voltage: 12, 24, 42, 50 VDC
  • Clamping Voltage: 15, 30, 48, 56 VDC
  • Operating Current: 2 A
  • Peak Surge Current: 015=125 A,
  • (10 x 1000 μs) 030=71 A,048=45 A,
  • CLN=125 A, SPK=500 A, 8/20
  • Frequency Range: 0 to 20 MHz
  • Insertion loss: < 0.1 dB at 20 MHz
  • SPD Technology Silicon Avalanche Diode (SAD), OPX-SPK model uses MOV
  • Connection Type: Clip
  • Operating Temperature: -40°C to +85°C
  • Dimensions (Inches): 1.25H x 0.375W x 2.0L
  • Weight: 1 oz
  • Certifications: UL 497B
Technical Specification
Surge Suppression Products
Contact our support department about your Surge Protection product.

Telephone: +1 607 721 8840
Toll-Free: +1 800 288 6169
Contact Support