Wye-Delta, Closed Transition Starting Fire Pump Controllers

Emerson Network Power > ASIA > Products > By Type > Fire Pump Controllers > Electric Fire Pump Controllers (600V max.) > Firetrol FTA1350 Wye-Delta, Closed Transition Starting
Firetrol® FTA1350 Wye-Delta, Closed Transition Starting Fire Pump Controllers are used with delta-wound squirrel cage motors. FTA1350 controllers are of the closed circuit transition type in which the motor circuit remains closed during the transition from start to run. The controller monitors, displays and records fire pump system information.
 
Actuating the controller via pressure, START push-button or deluge valve contact closes the start contactor connecting the motor to the line in the wye connection. The motor will draw approximately 33% of its normal inrush current and develop approximately 33% of its normal starting torque. After a time delay, the motor is automatically reconnected in delta, applying full voltage to the motor windings. During this transition, a resistor is connected to each phase, minimizing line disturbances and voltage drop during starting. These controllers are recommended especially for use with generator sets.
 
Firetrol fire pump controllers are listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers, CSA, Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code.
The following are included as standard with each controller:

  • Voltage surge protector
  • Main Disconnect Switch sized for connected motor horsepower and voltage
  • Fire pump Circuit Breaker
  • Motor contactor
  • Single handle Isolating Disconnect Switch/Circuit Breaker mechanism
  • Motor contactor
  • Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition
  • Built-in Start and Stop push-buttons to bypass automatic start circuits
  • Minimum Run Timer / Off Delay Timer
  • Daylight Savings Time Option
  • Weekly Test Timer
  • Elapsed Time Meter
  • Door mounted display/interface panel featuring a 128 x 64 pixel backlit LED Graphical Display, Membrane Type User Control Push-buttons and easy to read LED Indicators for:
  • POWER AVAILABLE
  • ALARM
  • TRANSFER SWITCH NORMAL (If unit ordered with Automatic Power Transfer Switch)
  • TRANSFER SWITCH EMERGENCY (If unit ordered with Automatic Power Transfer Switch)
  • SYSTEM PRESSURE LOW
  • PUMP RUNNING
  • DELUGE OPEN
  • REMOTE START
  • INTERLOCK ON
  • FAIL TO START
  • MOTOR OVERLOAD
  • EMERGENCY ISO SWITCH OFF (If unit ordered with Automatic Power Transfer Switch)
  • PHASE FAILURE
  • PHASE REVERSAL
  • AUTOMATIC SHUTDOWN DISABLED
  • OVERVOLTAGE
  • UNDERVOLTAGE
  • Digital Pressure Display
  • USB Host Controller and Port
  • Solid State Pressure Transducer
  • Data Log
  • Event Log (3000 Events)
  • True RMS Metering with simultaneous 3 Phase Display of Amps, Volts, Frequency, Pressure and Alarm Messages
  • Disk Error message
  • Disk Near Full message
  • Pressure Error message
  • Motor Over 320% message
  • Local Start message
  • Remote Start message
  • Emergency Start message
  • Fail To Start message
  • Undervoltage message
  • Overvoltage message
  • NEMA Type 2 enclosure
  • High Speed Open Serial Communications Port
  • Suitable for use as Service Equipment
  • Suitable for use as Service Equipment
  • Each standard controller comes with user confi gurable options for:
  • Interlock Alarm
  • Low Suction
  • User Defined Input
  • Low Pressure Audible
  • User Defined Input
  • Pump Run
  • Weekly Test
Features
SPECIAL ENCLOSURES
-T NEMA Type 3R (IEC IP22), Painted Steel
-E NEMA Type 4 (IEC IP66), Painted Steel
-F NEMA Type 4X (IEC IP66), #304 Stainless Steel,
-FXP NEMA Type 4X (IEC IP66), #304 Stainless Steel, Painted Finish, Unfinished**
-FD NEMA Type 4X (IEC IP66), #316 Stainless Steel, Unfinished**
-FDB NEMA Type 4X (IEC IP66), 12 Gauge, Seam Welded, #316 Stainless Steel, Polished and Brushed Finish
-FDP NEMA Type 4X (IEC IP66), #316 Stainless Steel Painted Finish
-G NEMA Type 12 (IEC IP54), Painted Steel ** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N Intermediate withstand rating
-P High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability.
ANTI-CONDENSATION SPACE HEATERS
-H 120 Volt Space Heater
-J 120 Volt Space Heater With Thermostat
-K 120 Volt Space Heater With Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater With Thermostat
-N 240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
AUTOMATIC POWER TRANSFER SWITCHES
FTA900 - generator set emergency supply
FTA950 - second utility emergency supply (Refer to publication SD900-20)
FTA901 - bypass isolation switch for generator set emergency supply
FTA951 - bypass isolation switch for second utility emergency supply (Refer to publication SD901-20)
ALARMS
-AC Extra contacts (normally open & normally closed) for remote indication, pump operating
-AF Audible and Visible low pump room temperature alarm
-AG Built-in reservoir low alarm
-AH Audible low suction pressure alarm
-AM Contacts for remote indication, pump fail to start
-AV Contacts for remote indication, low pump room temperature
-AW Contacts for remote indication, reservoir low
-AY Contacts for remote indication, low suction pressure
-AZ Low pump room temperature switch, mounted and wired
-BW Extra contacts for remote indication, phase failure/phase reversal
-BY Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable auto/manual reset, audible, visible and remote alarms, initiating pressure switch not included)
-CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch)
-EG Visible Relief Valve Discharge alarm
-EH Contacts for remote indication, relief valve discharge
-EJ Built-in fl ow meter on alarm
-EK Contacts for remote indication, fl ow meter on
-KH Contacts for remote indication, common output for any alarm
-JR Visible jockey pump running indication
-JT Audible and Visible jockey pump trouble indication
-P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
-PE Built-in low system pressure visible alarm with manual reset Contacts for remote indication, low system pressure
 -PT  Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
-HV Audible alarm device
MISCELLANEOUS
-DZ Test push-button and solenoid valve*
-ED Load shed circuits (Selectable power source and adjustable time delay to remove non-critical loads before starting)
-EL Series pumping, high zone controller
-EM Series pumping, mid zone controller(s)
-EN Series pumping, low zone controller
-FZX 400 VAC Operation (Controller labeled for 380-400VAC - Use with voltage code FZ)
-PY Motor space heater output contacts
-S Tropicalization
-SEI Seismic Certifi cation (in accordance with IBC)
-ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up)
-ZPN 5150 Ethernet Connectivity Module (Allows users to monitor limited controller status via a single computer or over a computer network)
-ZPM Serial Modbus RTU Communications Protocol (Allows users to monitor all aspects of the controller status via a RS485 communications network (system integration required). (Includes RS485 to twisted pair breakout module, optical isolation module (4000 ft. range), DC power supply and customer connection terminal blocks). Export packaging (Wooden crating to conform to IPPC Standards) FTA1000 - 1930