Firetrol FTA1000 Full Voltage Starting

Full Voltage Fire Pump Controller

 

 

Firetrol® FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps where the capacity of the power source permits full voltage starting. Full voltage is applied to the motor as soon as the controller is actuated. The controller monitors, displays and records fire pump system information.
Full voltage starting is simple and low cost and is preferred whenever the utility or emergency generator set will permit this type of starting.  

 

 

Firetrol fire pump controllers are listed by Underwriter's Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers and approved by Factory Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA-20, Installation of Stationary Pumps for Fire Protection, and NFPA 70, National Electrical Code.

 

The following are included as standard with each controller:

  • Voltage surge protector
  • Main Disconnect Switch sized for connected motor horsepower and voltage
  • Fire pump Circuit Breaker
  • Motor contactor
  • Single handle Isolating Disconnect Switch/Circuit Breaker mechanism
  • Motor contactor
  • Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition
  • Built-in Start and Stop push-buttons to bypass automatic start circuits
  • Minimum Run Timer / Off Delay Timer
  • Daylight Savings Time Option
  • Weekly Test Timer
  • Elapsed Time Meter
  • Door mounted display/interface panel featuring a 128 x 64 pixel backlit LED Graphical Display, Membrane Type User Control Push-buttons and easy to read LED Indicators for:
  • POWER AVAILABLE
  • ALARM
  • TRANSFER SWITCH NORMAL (If unit ordered with Automatic Power Transfer Switch)
  • TRANSFER SWITCH EMERGENCY (If unit ordered with Automatic Power Transfer Switch)
  • SYSTEM PRESSURE LOW
  • PUMP RUNNING
  • DELUGE OPEN
  • REMOTE START
  • INTERLOCK ON
  • FAIL TO START
  • MOTOR OVERLOAD
  • EMERGENCY ISO SWITCH OFF (If unit ordered with Automatic Power Transfer Switch)
  • PHASE FAILURE
  • PHASE REVERSAL
  • AUTOMATIC SHUTDOWN DISABLED
  • OVERVOLTAGE
  • UNDERVOLTAGE
  • Digital Pressure Display
  • USB Host Controller and Port
  • Solid State Pressure Transducer
  • Data Log
  • Event Log (3000 Events)
  • True RMS Metering with simultaneous 3 Phase Display of Amps, Volts, Frequency, Pressure and Alarm Messages
  • Disk Error message
  • Disk Near Full message
  • Pressure Error message
  • Motor Over 320% message
  • Local Start message
  • Remote Start message
  • Emergency Start message
  • Fail To Start message
  • Undervoltage message
  • Overvoltage message
  • NEMA Type 2 enclosure
  • High Speed Open Serial Communications Port
  • Suitable for use as Service Equipment
  • Suitable for use as Service Equipment
  • Each standard controller comes with user confi gurable options for:
  • Interlock Alarm
  • Low Suction
  • User Defined Input
  • Low Pressure Audible
  • User Defined Input
  • Pump Run
  • Weekly Test
Features
SPECIAL ENCLOSURES
-T NEMA Type 3R (IEC IP24), Painted Steel
-E NEMA Type 4 (IEC IP66), Painted Steel
-F NEMA Type 4X (IEC IP66), #304 Stainless Steel, Unfinished**
-FXP NEMA Type 4X (IEC IP66), #304 Stainless Steel, Painted Finish
-FD NEMA Type 4X (IEC IP66), #316 Stainless Steel, Unfinished**
-FDB NEMA Type 4X (IEC IP66), 12 Gauge, Seam Welded, #316 Stainless Steel, Polished and Brushed Finish
-FDP NEMA Type 4X (IEC IP66), #316 Stainless Steel Painted Finish
-G NEMA Type 12 (IEC IP54), Painted Steel ** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N Intermediate withstand rating
150,000 Amps RMS Sym.
-P High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be available for all horsepowers and voltages. Consult factory for availability.
ANTI-CONDENSATION SPACE HEATERS
-H 120 Volt Space Heater
-J 120 Volt Space Heater With Thermostat
-K 120 Volt Space Heater With Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater With Thermostat
-N 240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B 0-600 psi (0-42.25 bar) Pressure Transducer for Fresh Water Service
-C 0-300 psi (0-21.1 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
-D 0-600 psi (0-42.25 bar) Pressure Transducer for Sea Water, Foam or Copper Corrosive Service
COMBINED AUTOMATIC POWER TRANSFER SWITCHES
FTA950 - Generator/Utility emergency source
FTA951 - Bypass Isolation for Generator/Utility emergency source
ALARMS
-AC Extra contacts (normally open & normally closed) for remote indication, pump operating
-AF Audible and Visible low pump room temperature alarm
-AG Built-in reservoir low alarm
-AH Audible low suction pressure alarm
-AM Contacts for remote indication, pump fail to start
-AV Contacts for remote indication, low pump room temperature
-AW Contacts for remote indication, reservoir low
-AY Contacts for remote indication, low suction pressure
-AZ Low pump room temperature switch, mounted and wired
-BW Extra contacts for remote indication, phase failure/phase reversal
-BY Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable auto/manual reset, audible, visible and remote alarms, initiating pressure switch not included)
-CTS Built in Low Suction Pressure Alarm Panel (Includes selectable auto/manual reset, audible, visible and remote alarms and mounted and wired pressure switch)
-EG Visible Relief Valve Discharge alarm
-EH Contacts for remote indication, relief valve discharge
-EJ Built-in fl ow meter on alarm
-EK Contacts for remote indication, flow meter on
-KH Contacts for remote indication, common output for any alarm
-JR Visible jockey pump running indication
-JT Audible and Visible jockey pump trouble indication
-P Built-in alarm system (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
-PE Contacts for remote indication, low system pressure
-PT Built-in alarm system, 220 VAC supervisory power (Includes visible supervisory voltage normal indication and audible pump operating, phase failure and phase reversal indication)
MISCELLANEOUS
-ED Load shed circuits (Selectable power source and adjustable time delay to remove non-critical loads before starting)
-EL Series pumping, high zone controller
-EM Series pumping, mid zone controller(s)
-EN Series pumping, low zone controller
-FZX 400 VAC Operation (Controller labeled for 380-400VAC - Use with voltage code FZ)
-PY Motor space heater output contacts
-S Tropicalization
-SEI Seismic Certifi cation (in accordance with IBC)
-ZPA Customized, annual service display message (when factory programmed or programmed by Firetrol representative during start-up)
-ZPN 5150 Ethernet Connectivity Module (Allows users to monitor limited controller status via a single computer or over a computer network)
-ZPM Serial Modbus RTU Communications Protocol (Allows users to monitor all aspects of the controller status via a RS485 communications network (system integration required). (Includes RS485 to twisted pair breakout module, optical isolation module (4000 ft. range), DC power supply and customer connection terminal blocks). Export packaging (Wooden crating to conform to IPPC Standards) FTA1000 - 1930