Liebert GXT-MT Plus 6-10kVA

 
PRODUCTS

Liebert GXT-MT Plus 6-10kVA
Compact Tower UPS for High Performance Power Protection

 Liebert GXT MT Plus 6-10kVA Data Sheet

This product is available only in Hong Kong, Indonesia, Malaysia, Philippines, Singapore, Thailand and Vietnam

Emerson Network Power > ASIA > Products > By Type > AC Power and UPS > Network UPS > Liebert GXT-MT Plus 6-10kVA

The Liebert GXT MT+ features best-in-class power protection for critical applications with the use of true on-line double conversion technology. The Liebert GXT MT+ has a comprehensive specification that provides a higher level of availability to the IT equipment. It satisfies safety criteria and electromagnetic compatibility standards while offering intelligent monitoring and network management functions. This high performance UPS with proven reliability is available in a compact tower design.

Product Downloads
  • True on-line double-conversion technology
  • DSP technology guarantees high performance
  • 0.8 Output Power Factor
  • Wide input voltage range (110-300 VAC)
  • 0.99 input power factor correction
  • 50Hz/60Hz frequency converter mode
  • Configurable to energy saving mode (ECO)
  • Programmable power management outlets
  • Emergency power off function (EPO)
  • Generator compatible
  • Charger capacity expansion to 8A for long-run models
  • SNMP/USB/RS-232 communications
  • 3-stage extendable charging design for optimized battery performance
  • Extended runtime capability by building up additional battery resources
  • Maintenance bypass available
  • Optional N+X parallel redundancy
Features

MODEL/PART NUMBER 

GXT-6000MTPLUS230-9

PHASE

1 phase in / 1 phase out

CAPACITY

6000 VA / 4800 W

INPUT

Voltage
Range

Low Line Transfer

176 VAC ± 3% @ 100% load

110 VAC ± 3% @ 50% load

Low Line Comeback

186 VAC ± 3% @ 100% load

120 VAC ± 3% @ 50% load

High Line Transfer

300 VAC ± 3%

High Line Comeback

290 VAC ± 3%

Frequency Range

6000 VA / 4800 W

Phase

Single phase with ground

Power Factor

≥ 0.99 @ 100%load

OUTPUT

Output Voltage

208/220/230/240 VAC

AC Voltage Regulation (Batt. Mode)

± 1%

Frequency Range
(Synchronized Range)

46~54 Hz ~ 50 Hz / 56~64 Hz ~ 60 Hz

Frequency Range (Batt. Mode)

50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz

Current Crest Ratio

3:1 (max.)

Harmonic Distortion

≤ 3 % THD (Linear Load), ≤ 6 % THD (Non-linear Load)

Transfer
Time

AC Mode to Batt. Mode

Zero

Inverter to Bypass

Zero

Waveform (Batt. Mode)

Pure Sinewave

EFFICIENCY

AC Mode

89%

Battery Mode

88%

BATTERY

 

Standard
Model

Battery Type

12 V / 9 AH

Numbers

20

Typical Recharge Time

7 hours recover to 90% capacity

Charging Current (max.)

1.0 A

Charging Voltage

273 VDC ± 1%

Long-run
Model

Battery Type

Depending on applications

Numbers

18-20

Charging Current (max.)

4.0 A

Charging Voltage

273 VDC ± 1%

Runtime

Full Load

8 Minutes

INDICATORS

LCD Panel

UPS status, Load level, Battery level, Input/Output voltage,
Discharge timer, and Fault conditions

ALARM

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

100% to 105% for 10 minutes

Fault

Continuously sounding

PHYSICAL

Standard
Model

Dimension, D X W X H (mm)

592 X 250 X 576

Net Weight (kgs)

83

Long-run
Model

Dimension, D X W X H (mm)

592 X 250 X 576

Net Weight (kgs)

25

ENVIRONMENT

Operation Humidity

20-90 % RH @ 0- 40°C (non-condensing)

Noise Level

Less than 55dBA @ 1 Meter

MANAGEMENT

Smart RS-232

Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7,
Linux, Unix, and MAC

USB

Optional SNMP

Power management from SNMP manager and web browser

 

Technical Specifications