Chloride 80-NET guarantees 100% real power in every working condition thanks to its capability to power, without derating, all loads irrespective of the PF (leading or lagging). Its excellent power conversion efficiency, even at partial load, makes it outstanding value for customers who can greatly benefit from considerable cost savings throughout the service life of the Chloride 80-NET.

Using advanced digital control technology, Chloride 80-NET provides secure power protection, guaranteeing maximum uptime, reliability and flexibility for a wide range of mission critical applications including finance, health, transportation, telecommunications and data centers.

Technical Characteristics

Rating (from 60 - 120 kVA)

60

80

100

120

160

200

300

400

500

Output active power at 40°C (kW)

60

80

100

120

160

200

300

400

500

Apparent nominal output power
at 40°C (kVA)

60

80

100

120

160

200

300

400

500

Apparent nominal output power
at 25°C (kVA)

60

80

100

120

160

200

300

400

500

Input

Nominal primary mains input
voltage/voltage range (V)

400 (250 to 460), three phase + neutral

Nominal bypass input voltage/voltage
tolerance (V)

400 ±10% (380V, 415V selectable) the phase + neutral

Nominal input frequency/frequency
tolerance (Hz)

50 ± 10% (60 Hz selectable)

Input current distortion (THDi) (%)

<3

Primary input Power Factor

>0.99

Output

Nominal output voltage (V)

400 ±10% (380V, 415V selectable) the phase + neutral

Output voltage stability by load variation 0 - 100% (%)
- static
- dynamic



±1
Complies with IEC/EN 62040-3, Class 1

Nominal output frequency (Hz)

50 (60 Hz selectable)

Output frequency variation (%)
- with mains synchronization
- with internal reference


± 1 (2, 3, 4 selectable)
±0.1

Inverter overload capacity

125% for 10 min., 150% for 1 min.

Compatibility with loads

Any power factor (leading or lagging) up to 1
without output derating; crest factor up to 3:1

Automatic adjustment of nominal
output power with temperature

110% at 25°C, 100% at 40°C

General

Classification according to IEC/EN
62040-3

VFI - SS - 111

Operating temperature (°C)

0 - 40

Relative humidity
(without condensation at 20°C)

<95%

Protection level

IP 20

Frame Color

RAL 7016

Noise at 1 m (dBA)

62

62

65

65

67

67

69

70

71

AC/AC efficiency (%)*

up to 98%

Parallel configuration

up to 8 units

Dimensions and Weight

Height (mm)

1780

1800

Width (mm)

570

570

845

845

975

975

1675

1675

1900

Depth (mm)

858

UPS weight (kg)

270

270

380

380

495

590

1000

1160

1300

 

Technical Specification

 

FEATURES

BENEFITS

Total cost of
ownership (TCO)

 

 

• High efficiency Up to 95 % in
  double conversion mode.
  Up to 98 % in Digital interactive
  mode(DIM)

• Reduces carbon footprint and
  saves significant energy cost

• Unity Power factor (kVA=kW)

• Deliver 25% more active
  power(kW) than conventional
  architecture based UPS

• Wide voltage and frequency
  range

• Wide Voltage and  frequency range
  ensure UPS always run on utility
  power, prolong battery life

Availability

 

 

• Automatic power up gradation at 
  lower ambient temperature

• Deliver 10% more power at 25
  degree controlled ambient
  temperature.

• Full compatibility with all types of
  loads

• No deration through out the entire
  load PF range

• Input PF >.99 , THDi <3%

• Eliminate need for generator over
  sizing, excellent compatibility
  with generator

Adaptability

 

 

• Supports 1+N and N+1
  configuration

• Suitable to adjust as per today's
  dynamic electrical environment

• Scalable Up to 8 units in Parallel
  redundant architecture

• Maximum power availability

• Precharge hold off delay and
  power walkin function

• Sequentially start the UPS
  configured in Parallel architecture

• Flexible battery combination
  adopts 12Vx 40 to 50 cell
  design

• Original battery system can be
  modified and poor cells can be
  replaced without affecting UPS
  performance.

Infrastructure
Management

 

 

• 24x7 UPS real time monitoring
  powered by LIFE. technology

• Comprehensive real-time
  monitoring of over 150 parameter

• Powerful touch screen HMI

• User friendly man machine
  interface

• Loaded with advanced 
  communication options

• Compatible with most of the
  advanced communication platform
  including SNMP, MODBUS etc

 

Features and Benefits